Abstract
An experimental investigation has been conducted to determine the low-velocity critical heat flux (CHF) behavior on a single horizontal tube in a subcooled and low-quality two-phase crossflow of R-113. Data were obtained over a range of velocities (up to 0.3 m/s), subcooling (0 to 14 K), and qualities (0 < x < +30 percent) at two pressures. There was a linear decrease in the CHF with increasing quality up to about 10 percent quality; then, due to a flow regime transition, the CHF remained relatively constant. A correlation has been developed which predicted well the subcooled and low-quality region CHF condition in the linearly decreasing portion of the curve. Data from the literature are also predicted well.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.