Abstract

Abstract Electric cables can contribute to the spread of fire through the insulating layer. This paper focuses on their properties characterizing the initiation of fire. Samples of ethylene-based cable insulation were tested using a cone calorimeter by exposing them to external heat flows of six different values (25 kW m−2 – 50 kW m−2). Time to initiate flame burning was observed. The critical heat flux (depending on the method of calculation was in the range 2.94 kW m−2 – 4.59 kW m−2) and the thermal response parameter (342 kW s−0.5 m−2) was calculated from the time of initiation and external heat flow dependence.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.