Abstract
This paper presents the critical egress parameters that influence emergency evacuation in a typical hospital building. A parametric study of a 20-story hospital building is conducted using a computer model “Pathfinder” to simulate the evacuation efficiency and assess the influencing parameters. The main egress parameters that influence the evacuation efficiency, including the location of stairways, number of stairways, location of the fire, exit width, and number of low-speed occupants are varied. Two scenarios are simulated: one being the regular (practice) evacuation drill and the other is the actual fire drill. The result shows that the location of stairways significantly affects the total evacuation time with the optimal stairway arrangement consisting of one stairway outside the core of the building. Similarly, the story level at which the fire occurs is another key parameter with fires at lower levels being critical to dictating the evacuation time in a hospital building. The total evacuation time when the fire occurs between the third and sixth floor is found to be 170 min which is 36% and 15% higher than fires at the top story levels (15–18th floor) and the intermediate story levels (9–12th floor), respectively.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.