Abstract

With high critical heat flux (CHF) and heat transfer coefficient (HTC), spray cooling is considered as one of the most promising thermal management technologies for high-power electronic devices. To increase its cooling performance, a closed-loop experimental rig was constructed to study the effects of spray and system parameters on heat transfer enhancement by R410A. The best cooling performance can be achieved under optimal subcooling degree of 17 °C and nozzle diameter of 0.56 mm. When the compressor frequency reaches the upper limit of 90 Hz, maximum CHF and HTC on flat surface are 301.6 W/cm2 and 91.7 kW/(m2·K). To further improve CHF, mechanism of heat transfer enhancement by square pin finned surface was revealed in terms of droplet splashing. With fin width of 0.5 mm and height of 3 mm, CHF as high as 522.1 W/cm2 and peak HTC of 407.0 kW/(m2·K) are reached, while maintaining the cooling surface temperature lower than 55.6 °C. Compared to flat surface, CHF and HTC are enhanced by around 73.4% and 3.5 times, respectively. Based on the experimental data, CHF correlation applicable to pin finned surface was obtained with precision of ±12.4% by introducing fin height and width.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.