Harmonic blocking is usually applied by converter transformer differential protection to prevent protection mal-operation during an inrush condition, but it may incorrectly block the protection during an internal fault. This paper first makes an in-depth analysis on factors that lead to differential protection failure to trip for converter transformer internal faults. The main factor responsible for the protection failure to trip is half-cycle saturation of the converter transformer core, which results from the dc component in the fault current. This suggests that harmonic blocking may not be suitable for differential protection of converter transformers to identify inrush conditions. In this regard, this paper proposes a novel method using mathematical morphology to effectively discriminate between the conditions caused by inrush and internal faults. This method implements the waveform symmetry criterion and improved morphological gradient criterion to distinguish between these two conditions. The effectiveness of the proposed method is evaluated based on extensive simulation, and the presented results show that the proposed method can ensure operation for all types of internal faults. Additionally, this method improves the accuracy of inrush identification, even in extreme cases, such as sympathetic inrush and inrush with current transformer saturation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.