Abstract
The design approach and operation of a newly developed package plant treating domestic sewage from single households were evaluated. Combining submerged aerated filter (SAF) technology with jet aeration and incorporating both into a compact and shallow tank resulted in a cost-effective treatment solution. A trial unit was permanently installed at a rural site, serving a single household. Jet aeration proved to be the best aeration method for the shallow bioreactor design. Further trials revealed a 50% reduction in suspended solids (SS) through the use of a static effluent filter and found that annual plant maintenance was vital to sustain stable operating conditions. Despite high variations in influent conditions, the trial unit produced good effluent quality during steady-state operation. Average effluent BOD5, COD and SS values were 19.6 mg l(-1), 98 mg l(-1) and 32 mg l(-1) achieving overall removal efficiencies of 94.2%, 85.9% and 87.6% respectively. However, effluent ammonia nitrogen (NH4-N) levels were found to be inconsistent varying from 9 mg l(-1) to over 60 mg l(-1).
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.