This paper is concerned with Proportional-Integral-Plus (PIP) control of ventilation rate in mechanically ventilated agricultural buildings. In particular, it develops a unique fan and throttling valve control system for a 22m3 test chamber, representing a section of a livestock building or glasshouse, at the Katholieke Universiteit Leuven. Here, the throttling valve is employed to restrict airflow at the outlet, so generating a higher static pressure difference over the control fan. In contrast with previous approaches, however, the throttling valve is directly employed as a second control actuator, utilising airflow from either the axial fan or natural ventilation. The new combined fan/valve configuration is compared with a commercially available PID-based controller and a previously developed scheduled PIP design, yielding a reduction in power consumption in both cases of up to 45%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.