Abstract

The nature and causes of corrosive sulfur induced failures are examined in oil-filled transformers and shunt reactors. Copper sulfide, which is formed when the corrosive sulfur in a mineral oil reacts with the copper conductors, is likely to diffuse into the paper tapes insulating the conductors. Since copper sulfide is partially conducting, the dielectric losses of the contaminated oil-impregnated-paper tapes are markedly increased; paper tapes in close proximity to the copper conductors are found to attain tan delta values > 1.0 even at room temperature. It is highly likely that thermal instabilities develop at those sites at operating temperatures, leading to increased loss currents and, ultimately, short circuits between the turns. This sequence of events is substantiated by evidence from the field, which indicates large areas of thermally degraded insulations and charred breakdown regions along the coils, the extent of which becomes more pronounced at higher operating temperatures (toward the top of the windings).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.