Abstract
The behavior of corrosive sulfur in mineral oils is examined in terms of the failures observed in transformers, the surfaces of the copper sulfide covered conductors and degraded paper insulating tapes. The role of dissolved gas analysis (DGA) in the evaluation of the risk of copper sulfide formation is described. The degree of corrosiveness of some sulfur compounds is examined and compared using a Kraft paper wrapped-copper test (standard IEC 62535). The occurrence of DBDS as the most relevant corrosive compound is compared with the presence of other corrosive species in insulating mineral oils. A number of mitigation techniques for corrosive sulfur are described and evaluated.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Dielectrics and Electrical Insulation
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.