Abstract

This work investigates the corrosion failure of the chlorinator’s copper pipes in a rural water disinfection station. For this purpose, some corroded samples were provided from the failed pipes and investigated using the X-ray diffraction (XRD) and the scanning electron microscope (SEM) equipped with the energy-dispersive X-ray spectroscopy (EDS). Also, an experimental setup was designed to study the role of the electrolyte formation on the copper pipes. This experimental setup demonstrated that the main factor of pipe failure was the formation of a corrosive electrolyte layer with varying chlorine (presented due to gas leakage) concentration during a day. The electrochemical impedance spectroscopy (EIS) confirmed that variations in the chlorine concentration had an unexpected effect on the corrosion rate. Furthermore, it was found that the main phase in the corrosion products was cupric chloride hydroxide (Cu2(OH)3Cl) with many porosities and cracks. These defects provide suitable places for the formation of the corrosive electrolyte and the following corrosion which ultimately led to the failure of the copper pipes.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.