Abstract

The failure analysis of a seawater fire protection system of oil and gas processing facility was observed in this paper. The fire protection pipe line & hull seawater filter were made of CuNi 90/10. Severe deep pits and fracture were observed at bottom of jockey pump spool pipe and hull seawater filter. Visual observation, scanning electron microscope, energy dispersive spectroscopy, x-ray diffractometry were employed in the present failure analysis. The oxygen exposure on CuNi 90/10 of Seawater Fire Protection system had a significant impact on failure and was exacerbated by the presence of chloride exposure.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.