Abstract

To improve the reliability and quality of electric power systems, preventive diagnosis and regular maintenance of high voltage capacitors are required. Dielectric response measurements in both time domain and frequency domain are potential tools for assessing the condition of dielectric of high voltage capacitors. Modern measurements in time domain include polarisation and depolarisation current (PDC) and recovery voltage (RV) measurements, whereas frequency domain measurements include dielectric dissipation factor (DDF) measurements. To understand the physical behaviour due to the effect of moisture and aging, a detailed analysis of dielectric test results is required. In this paper, a detailed equivalent circuit model of the insulation system in high voltage capacitors has been given. The values of the parameter of the circuit model have been calculated from the dielectric test results. Correlation between the physical condition of the insulation and the equivalent model parameters are also presented in this paper.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.