Abstract

The insulation diagnostic test and the AC breakdown test were performed under off-line using the 3.3 kV class induction motor which have been served for 10 years. These tests were conducted in means of nondestructive and destructive test. In this paper, we compared the correlation between the nondestructive and destructive test. Furthermore we setup an experimental condition with moisture and compared the insulation characteristics between moist and dry sample. From the results of the nondestructive and destructive test, it was found that the second AC current, which is the previous step of insulation breakdown, suddenly increased at a point of around 8.5 kV. The insulation breakdown of moist sample occurred at 12-14 kV, which is 4-5 kV lower than dry sample.