Abstract
Positive and negative small ions, aerosol ion and number concentration and dc electric fields were monitored at an overhead high-voltage power line site. We show that the emission of corona ions was not spatially uniform along the lines and occurred from discrete components such as a particular set of spacers. Maximum ion concentrations and atmospheric dc electric fields were observed at a point 20 m downwind of the lines. It was estimated that less than 7% of the total number of aerosol particles was charged. The electrical parameters decreased steadily with further downwind distance but remained significantly higher than background.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.