Abstract

Overhead distribution lines can be seriously damaged from lightning events because both direct and indirect events can cause flashovers along the line. The lightning performance of such power lines is usually computed neglecting the effect of corona discharge along the conductors: in particular, the corona discharge determined by the indirect lightning event is taken into account only by few researchers because it can have meaningful impacts only in few cases. However, when we deal with overhead distribution lines with high Critical Flashover value (CFO) and small diameters, the corona discharge caused by indirect events has to be taken into account. This paper shows the effects of corona discharge in the lightning performance computation of overhead distribution lines. The analysis will involve different configurations in terms of line diameter and air conditions, focusing on the negative effect of corona discharge in the number of dangerous events that determine line flashovers.

Highlights

  • Lightning is one of the most important issues in terms of protection of transmission and distribution lines [1]. Their protection requires an accurate evaluation of the insulation coordination system [2] as well as a correct computation of the number of dangerous events striking the line per year. The latter parameter is usually computed through the lightning performance procedure—a high number of lightning events, each of them characterized by different parameters extracted from their own Probability Density Function (PDF), is generated and their effects on the power system are computed through a simplified method [1,3,4] or through a numerical code [5,6,7,8,9]

  • This paper analysed the importance of corona discharge in the lightning performance computation, taking into account the effect of corona discharge caused by indirect events

  • The corona effect has been implemented in the FDTD code for lightning-induced voltages computation following the approach proposed in Reference [12]

Read more

Summary

Introduction

Lightning is one of the most important issues in terms of protection of transmission and distribution lines [1]. (ii) In References [16,17] the 3D–FDTD code simulates the corona discharge giving different values to the conductivity of the cell where corona effect is located; the main difference with the previous approach is that here the q-v characteristic results as an output calculation from the numerical integrations, while in the previous one appears as an input of the problem Both approaches lead to the same conclusions, that is, the enhancement of the induced voltage. The aim of this work is to evaluate the effects of corona discharge in the lightning performance computation of an overhead distribution line and to make some sensitivity analysis on the parameters that mainly affect the enhancement of the number of dangerous events striking the line.

The Corona Effect
Implementation of Corona Discharge
Corona Effect Influence on the Lightning Performance
Surface Conditions
Conductor Diameter
Air Humidity
Findings
Conclusions