Abstract

Most wind farms currently being installed are based upon doubly fed induction generator (DFIG) or direct-drive synchronous generator (DDSG) technology. Given that one of the impacts of introducing distributed generation is an alteration of steady-state power flows and voltages, both technologies are capable of providing local voltage support. Wind farms may, therefore, be included in optimal power flow (OPF) calculations to minimise fuel cost and/or network losses. The IEEE 30-bus system is considered as a case study, comparing fixed-speed induction generator (FSIG) requirements with DFIG capability. Results are presented for a range of DFIG capability modes, at varying system load and wind farm penetration levels. A significant reduction in losses can be achieved by suitable co-ordination of DFIG reactive power import/export, operating within typical grid code specifications. It is shown that the dynamic variability of reactive power requirements is readily accommodated by the power system. Finally, implementation options for the scheme and incentivising strategies are considered. Copyright © 2010 John Wiley & Sons, Ltd.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.