Abstract

A coordinated system protection scheme (SPS) against voltage collapse based on model predictive control and tree search is presented. It optimally coordinates dissimilar and discrete controls such as generator, tap changer, and load shedding controls in presence of soft and hard constraints on controls as well as voltages and currents in the network. The response with the coordinated SPS is compared to an SPS based on local measurements using simulation of the Nordic 32 test system. In terms of the amount of load shedding required to restore voltage stability, the simulations indicate that load shedding based on local criteria is near optimal in the system studied. However, when generator controls are also considered as emergency controls, the coordinated scheme reduces the amount of required load shedding by 35% compared to the local scheme.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.