Abstract

In this paper, the challenging multi-contingency transient stability constrained optimal power flow problem is partitioned into two sub-problems, namely optimal power flow (OPF) and transient stability control, solved in turn with conventional well trusted power system analysis tools instead of tackling it directly using a complicated integrated approach. Preventive multi-contingency transient stability control is carried out with generation rescheduling based on trajectory sensitivities using results obtained from a conventional transient stability simulation. A new iterative approach is proposed to optimally redistribute the generation from the critical machines to noncritical machines with the help of conventional OPF. Results on the New England 10-machine 39-bus systems demonstrate that the proposed method is capable of handling multiple contingencies and complex power system models effectively with solution quantity and time comparable with conventional integrated approaches.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call