Abstract

Cascading commutation failure (CF) caused by the reactive power interaction between HVDC is one of the new forms of cascading failures in multi-infeed HVDC systems. However, the concept and mechanism of cascading CF have not been explained clearly, and few studies have been devoted to control strategy for cascading CF mitigation considering reactive power interaction. In this paper, the cascading CF is defined and novel coordinated control strategy for cascading CF mitigation is proposed. Firstly, the mechanism of cascading CF in multi-infeed HVDC systems is analyzed. Then influence degree of HVDC on the power system stability is evaluated considering both active power impact and reactive power interaction, based on which novel coordinated commutation failure prevention as well as voltage dependent dc current order limiter is developed to mitigate cascading CF. Simulation results based on CIGRE HVDC benchmark model in PSCAD/EMTDC verify the effectiveness and advancement of proposed strategy on cascading CF mitigation.