The AC-DC hybrid distribution network based on modular multilevel converters (MMC) is beneficial for receiving distributed generation (DG), energy storage devices and DC loads. Therefore, the coordinated control of MMC and DG is very important for its safe operation. In this paper, doubly-fed induction generator (DFIG) are used as DG, and the control strategies of DFIG and MMC systems are analyzed. The system modeling research is carried out on a real time digital simulator (RTDS) platform. Then based on MMC control, an improved adaptive Crowbar circuit is proposed to improve inverter AC system low-voltage ride-through (LVRT) capability. The results show that the coordinated control strategy can better compensate the reactive power of the system to achieve LVRT, and verify the effectiveness of the control strategy adopted by the converter station.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.