Abstract
The paper presents methods for mitigating subsynchronous interaction (SSI) between doubly fed induction generator (DFIG) based wind farms and series capacitor compensated transmission systems. SSI damping is achieved by introducing a supplemental control signal in the reactive power control loop of the grid side converter of DFIG and full-scale frequency converter wind turbines, as well as in the reactive power control loop of the HVDC onshore multimodule converter (MMC) of offshore wind farms. This paper also investigates the impact of the phase imbalance series capacitive compensation concept that was introduced in the 1990s as a subsynchronous resonance countermeasure on SSI damping. The validity and effectiveness of the proposed methods are demonstrated on a test benchmark through time domain simulation studies using the ElectroMagnetic Transient Program (EMTP-RV).
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.