Abstract

The operation of ac connected wind power plants equipped with full power converter wind turbines under deep voltage sags on the main ac grid is analyzed. It is identified that standard control schemes, based on the strict application of grid codes, can lead to instability problems when this kind of severe disturbances occurs. A coordinated control scheme is proposed to operate the system, ensuring fault ride through capability. An index alerts of instability proximity and allows to activate active power and reactive power regulation to guarantee safe operation during faults. This paper describes the proposed control approach and demonstrates its performance by means of dynamic simulations with DIgSILENT Power Factory.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.