Abstract

We analysed the protective cooperation between a reclosing system and a flux-coupling type superconducting fault current limiter (SFCL). In order to compare the recovery behavior, the SFCLs without or with a neutral line between secondary coil and superconducting elements were prepared. Most of power grid has a reclosing system, which controls the circuit breaker by the sequential procedure, to cope with various faults. Generally, fast recovery of the SFCL was very important for stable operation between the reclosing system and the SFCL. The reclosing cycles (CO-t-CO-t-CO) for the experiments was set to 5-10-7-20-5. Recovery time in a flux coupling type SFCL without a neutral line was lengthened due to unequal quench between superconducting elements and it caused decrease of the maximum applied voltage. In the meantime, recovery time in the SFCL with a neutral line was shortened due to simultaneous quench between the elements. So, applied voltage of the power system could be higher within same reclosing system. As turn's ratio between secondary coil and superconducting elements was increased, recovery time was longer due to increase of their power. We confirmed that a flux-coupling type SFCL with a neutral line was more profitable for good cooperation between superconducting elements and a reclosing system.