Abstract
Abstract Small scale tests oruan open recirculating cooling system with a cooling water flow of 10 m3/h conducted for a period of two years have shown that ozone could be a viable alternative to chlorine and other commonly used biocides. An average ozone dosage of 0.05 mg/L was applied continuously to the cooling water. Corrosion rates of copper alloy samples immersed in ozonized water were lower than the rates of samples in non-ozonized water. No corrosion was detected for the Cr-Ni steel alloys DIN 1.4306 and DIN 1.4404 as well as for titanium either in the presence or absence of ozone in water. This is ascribed to the formation of a thin protective layer in both cases. A pilot plant has been set up at the EVS Heilbronn coal-fired power station in West Germany in order to confirm the results obtained on small scale. The open recirculating cooling system has a cooling water flow of 1,000 m3/h and is fed by conditioned Neckar river water. An air-fed ozone generator is used to ozonize a 10% side stream of ...
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.