Abstract
The use of cool storage in conjunction with residential lithium bromide absorption chillers allows for improved operating conditions of the cooling subsystem. Significant performance degradation in the absorption cooling capacity is evident whenever the chiller cycles on and off during periods of low cooling demand. The capability of providing storage for the chiller out-put prevents short-term cycling of the absorption machine and significantly improves the seasonal average coefficient of performance of the cooling system. Cool storage can also be utilized to allow for a lower cooling capacity of the absorption unit (lower tonnage), without decreasing the ability of the subsystem to meet the cooling demands of the building. The size of cool storage can, in fact, be optimized by evaluating the ability of the cool storage component to minimize cycling of the absorption machine and in meeting the cooling demands on a smaller tonnage chiller.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.