Abstract
This paper is responsive to needs to describe and predict the environmental effects from power plant cooling ponds. A study was made to determine atmospheric and pond surface conditions required for steam fog to occur from power plant cooling ponds, to define the dimensions of the fog, and to collect data on deposition of ice. Data, collected principally at the 4-Corners Plant over a three-year period, included water surface temperature, ambient meteorological conditions and occurrence and magnitude of steam fog and ice deposition. With strong winds, the fog extended onshore without lifting. With light winds, the fog extended some distance onshore but then lifted to form stratus. With almost calm winds, the steam fog lifted over the pond and drifted downwind as stratus. Steam fog was observed in winds to 28 mph, air-water temperature differences from 21.5° to 68°F and in atmospheric stability categories C, D, E, and F. A fog index number, Ar/(es — ea)°F/mbs, was defined and used for data interpretation, w...
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.