Abstract
The cooling performance of a CO 2 cycle must be improved to develop a competitive air-conditioning system with the conventional air-conditioners using HFCs. In this study, the cooling performance of a variable speed CO 2 cycle was measured and analyzed by varying the refrigerant charge amount, compressor frequency, EEV opening, and length of an internal heat exchanger (IHX). The basic CO 2 system without the IHX showed the maximum cooling COP of 2.1 at the compressor discharge pressure of 9.2 MPa and the optimum normalized charge of 0.282. The cooling COP decreased with the increase of compressor frequency at all normalized charges. The optimum EEV opening increased with compressor frequency. Simultaneous control of EEV opening and compressor frequency allowed optimum control of the compressor discharge pressure. The optimal compressor discharge pressure of the modified CO 2 cycle with the IHX was reduced by 0.5 MPa. The IHX increased the cooling capacity and COP of the CO 2 cycle by 6.2–11.9% and 7.1–9.1%, respectively, at the tested compressor frequencies from 40 to 60 Hz.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.