Abstract

The main purpose of this study was to evaluate the cooling performances of two different types of cross-flow indirect evaporative coolers (IECs) operated in two different operation modes: general and regenerative. The cooling performances of the IECs were tested in each operation mode in an environmental chamber. In the general mode, the secondary air stream passing through the wet channels was the return air from the conditioned zone; whereas, in the regenerative mode, a portion of the primary air leaving the dry channels was redirected to the secondary channels. The IEC performances were measured under constant primary air inlet temperature and humidity ratio with variations of the primary airflow. As indexes of the IEC performance, the wet-bulb effectiveness and cooling capacity of both IECs in each operation mode were estimated based on the measurement data. The experimental results revealed that, in the general operation mode, both IECs exhibited higher sensible cooling performances in terms of wet-bulb effectiveness than in the regenerative mode in a 100% outdoor air system application.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.