Thyristor valve design merits are inherited and new developed high power rating thyristors are used in the valve design. The thyristor control unit (TCU) and snubber circuit are optimized for a high reliability and low loss of thyristor valves. Two 12-pulse converters are connected in series as one converter per pole. The converters use a double valve MVU structure. A careful designed rigorous type test program has been followed to verify the valve and converter design. A single valve is comprehensively dielectric type tested and operational type tested. High voltage valve hanging structure, low voltage valve hanging structure and MVU, plus the series connected valve simulator, are valve supporting structure dielectric tested and MVU dielectric tested. The test results indict that the valve voltage and converter design and protection are proper and there is a substantial margin in operation since, for most of the operational tests, the test parameters were globally more severe than specified.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.