Abstract

This work presents an experimental study on the mean Nusselt number, friction factor and enhancement efficiency characteristics in a round tube with short-length twisted tape insert under uniform wall heat flux boundary conditions. In the experiments, measured data are taken at Reynolds numbers in a turbulent region with air as the test fluid. The full-length twisted tape is inserted into the tested tube at a single twist ratio of y/ w = 4.0 while the short-length tapes mounted at the entry test section are used at several tape length ratios ( LR = l s/ l f) of 0.29, 0.43, 0.57 and 1.0 (full-length tape). The short-length tape is introduced as a swirling flow device for generating a strong swirl flow at the tube entry before decaying along the tube. On the other hand, the full-length tape ( LR = 1.0) is expected to produce a strongly swirling flow over the whole tube. The variation of heat transfer and pressure loss in the form of Nusselt number ( Nu) and friction factor ( f) respectively is determined and depicted graphically. The experimental result indicates that the short-length tapes of LR = 0.29, 0.43 and 0.57 perform lower heat transfer and friction factor values than the full-length tape around 14%, 9.5% and 6.7%; and 21%, 15.3% and 10.5%, respectively. In addition, it is apparent that the enhancement efficiency of the tube with the short-length tape insert is found to be lower than that with the full-length one. The mean deviation between measured and correlated values of the Nusselt number is in the order of ± 7% in the range of Reynolds numbers from 4000 to 20,000.