Abstract

The effort to make the production of electrical energy much more environmental-friendly, large conventional power plants will be replaced by several smaller regenerative power plants. In order to improve stability and controllability, these smaller power plants are supposed to control the active power, the reactive power and the power factor in the medium voltage grid like conventional power plants. This paper will discuss three different methods to control the medium-voltage power factor from the low voltage side in consideration of parasitic effects from cables and transformers to fulfill the guidelines at the grid connection point. A method with a self-learning-algorithm will be implemented and proven by simulations and measurements on a test bench with inverter and 400 V to 10 kV grid transformer. The self-learning-algorithm will give the opportunity to reach every required power factor at the grid connection point.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.