Abstract
Because of the discrepancies between design parameters and actual plant data, controller tuning is required during the power testing of a new plant. Furthermore, after a certain period of operation, the effects of aging on the sensors and components cause the system performance to change. With the recent improvements in control system hardware, a better control algorithm can be implemented to ensure the safety of the system. Control system tuning and modification are necessary to keep the system at peak performance. The Taiwan Research Reactor (TRR) is a heavy water-type research reactor. During power operation, a large overshoot in neutron power was observed during a change in thermal power demand. Hence, the dynamic performance of the TRR power regulating system was degraded. From the control system point of view, it is worthwhile to determine the cause of the degraded control system and to tune the corresponding controller setting to achieve better performance. In this paper, the performance of the TRR power regulating system is simulated, the course of the large over-shoot in neutron power is identified, and the control system performance is modified.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.