Abstract

This paper describes the use of an unbalanced control strategy to solve the faults occur in AC grid side of High voltage direct current based on Voltage Source Converter (VSC-HVDC) system. This method divides the voltage and current parameters into negative-sequence and positive-sequence. It can be obtained that the negative-sequence appears as double-frequency component in the positive-sequence synchronous reference frame; while, it appears as dc component in the negative-sequence synchronous reference frame. To mitigate the unfavourable impact of the unbalance fault, such as the DC link ripples, the dual vector control algorithm in dq synchrounous reference frame is designed. Simulation results demonstrate the validity and the effectiveness of the proposed control scheme.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.