Abstract

Power quality and voltage control are among the most important aspects of the grid-connected power converter operation under faults. Nonsinusoidal current may be injected during unbalanced voltage sag, and active or/and reactive power may include double frequency content. This paper introduces a novel control strategy to mitigate the double grid frequency oscillations in the active power and dc-link voltage of the two-stage three-phase grid-connected photovoltaic (PV) inverters during unbalanced faults. With the proposed control method, PV inverter injects sinusoidal currents under unbalanced grid faults. In addition, an efficient and easy-to-implement current limitation method is introduced, which can effectively limit the injected currents to the rated value during faults. In this case, the fault-ride-through operation is ensured, and it will not trigger the overcurrent protection. A non-maximum power point tracking (non-MPPT) operation mode is proposed for the dc–dc converter. The mode is enabled under severe faults when the converter cannot handle the maximum PV power. Finally, experimental validation is provided by implementing a method in an experimental setup, including a 2 kW PV inverter.