Abstract
The influence of location of airborne particle source, ventilation rate, air inlet size, supply air velocity, air outlet location, and heat source on the distributions of airborne particle concentration and draught risk in an operating room is investigated. The investigation is carried out by using flow program with the k-e model of turbulence. Based on a standard case, five cases, each with one changed parameter, are computed, and the detailed field distributions of air velocity, temperature, airborne particle concentration, and draught risk are presented. The parametric study concludes that, for a better air quality and thermal comfort, it is desirable to use a higher inflow rate, a larger inlet area, and a uniform velocity profile of supply air. Outlet location and heat source have little influence on the distributions ofthe particle concentration in the room. It has also been found that the distributions of particle concentration in the recirculating zone are very sensitive to the location of the particle sources.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.