Abstract

This paper presents three control methods for a hybrid active power filter (HAPF), which is reduced the rating of active converter. Main circuit topology and their principles of the HAPF were discussed in detail. The single-phase equivalent circuits in harmonic domain of the HAPF are also given. Experiment waveforms were gotten from a laboratory prototype, rated at 10kVA. Experiment results prove the active converter rating accounts for only 4.42% of the HAPF rating while the total harmonic distortion of the source current is reduced to 4.25% from 26.95% with the combined control method, which is better than the other control methods.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.