Abstract

The dynamic voltage restorer (DVR) has become popular as a cost effective solution for the protection of sensitive loads from voltage sags. Implementations of the DVR have been proposed at both a low voltage (LV) level, as well as a medium voltage (MV) level; and give an opportunity to protect high power sensitive loads from voltage sags. This paper reports practical test results obtained on a medium voltage (10 kV) level using a DVR at a distribution test facility in Kyndby, Denmark. The DVR was designed to protect a 400 kVA load from a 0.5 p.u. maximum voltage sag. The reported DVR verifies the use of a combined feed-forward and feed-back technique of the controller and it obtains both good transient and steady state responses. The effect of the DVR on the system is experimentally investigated under both faulted and nonfaulted system states, for a variety of linear and nonlinear loads. Variable duration voltage sags were created using a controllable LV breaker fed by a 630 kVA distribution transformer placed upstream of the sensitive load. The fault currents in excess of 12 kA were designed and created to obtain the required voltage sags.