Abstract

A variable refrigerant flow (VRF) unit and outdoor air (OA) processing unit combined air conditioning system is proposed as a solution for ventilation problems in VRF systems. System structure and control strategies are addressed. Simulation platform is established based on component and sub-system models developed. Control and energy performances analysis are then put forward under various conditions. It is found that the combined system could maintain all the zones at their specific set-points within small errors no matter set-points of the zones are the same or different. In addition, indoor air quality can be ensured. Energy efficiency characteristics of the combined system are greatly affected by the OA supply temperature of the OA processing unit, which opens up the opportunity of minimizing the energy consumption of the combined system through optimal control strategy. Results reveal that the best OA supply temperature can be obtained through optimizing part load ratio of the OA processing unit to a range in which the system operates with high efficiency.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.