Abstract
This paper includes the theoretical analysis and experimental validation of a control strategy for the direct power and current control of grid-connected inverters. The studied control strategy allows for constant active and reactive power delivery during unsymmetrical faults and with supply voltage distortion, without the use of a PLL or FLL. It has been proven that only positive sequence current harmonics are necessary to deliver constant P and Q during unbalanced grid faults. The resulting stationary frame control has been experimentally validated during unbalanced voltage sags and swells.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.