Abstract

For simulation of centrifugal chiller system with differential algebraic equations, consistent initial conditions are difficult to obtain due to the two-phase refrigerant cycle and the connections between several components. Existing rigorous initialization methods are not suitable for the particular problems in centrifugal chiller simulation, such as the surge instability. In this paper, the dynamic model of a water-cooled centrifugal chiller is developed in Modelica with Dymola and the TLK/IfT Library (TIL). A preprocessing scheme and a direct initialization method are proposed for the consistent initialization of chiller DAE system. Simulation results have shown the effectiveness of the proposed modelling framework and the initialization method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.