Abstract

That the problem of computing the capacity limit of a radial distribution system can be formulated as a second-order cone program is shown. The implications of the conic programming formulation are 2-fold. First, the load capability of the radial system can be obtained using existing efficient implementations of polynomial time interior-point algorithms, thus avoiding the need for running a sequence of load flow solutions. Secondly, the conic objective function yields a voltage stability indicator (SI). This indicator quantifies the maximum percentage by which the current load profile can be uniformly increased before voltage collapse occurs. The proposed method is validated by computing the load capability and voltage SIs of 11 different distribution systems. Comparisons are carried out with five previously published voltage SIs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.