Abstract

AbstractStiction in a control valve generates limit cycles which can propagate to the connecting units, resulting in plant‐wide oscillations and impacting the overall process performance. For stiction confirmation, Choudhury et al. [Choudhury et al., CJChE 2007;85:208–219] introduced the controller gain change method, which is based on the change in the oscillation frequency due to changes in the controller gain. In this paper, we show that this method can fail to accurately isolate and confirm the presence of the sticky valve in interacting multi‐input multi‐output systems. We propose a strategy based on the magnitude of relative change in oscillation frequency due to changes in controller gain to overcome the limitations of the existing method. The effectiveness of the proposed method is demonstrated using simulation studies.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.