Abstract

Critical heat flux (CHF) of the fluoroketone fluid FKE-774 in vertical microgap channels is explored, with a focus on submillimeter spacings. Experiments were conducted using a 20 mm × 20 mm heated aluminum surface. Microgap channel spacings were decreased down to 0.3 mm, providing channel aspect ratios (height/spacing) as high as 67. In the limit where channel spacing is large, CHF was found to be 140 kW/m2 for saturated boiling at atmospheric pressure. A reduction in CHF of 55% was observed for the largest channel aspect ratio investigated. Results for degradation of the CHF limit with decreasing microgap spacing are compared to a correlation available in the literature and show a roughly hyperbolic dependence on channel aspect ratio (height/spacing) for aspect ratios larger than 10.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.