Abstract

On Load Tap Changer (OLTC) failure occurs is due to the insulation degradation and contacts failure inside it. Other than that, contacts wear influences the OLTC performances. The worn contacts will cause hotspots in the OLTC tank and cause the insulating oil to degrade faster. As a result, this will lead to the damage of complete transformer unit. Thus, the research work that has been carried out applied the Dissolved Gas Analysis (DGA) via latest Duval Triangle method during the diagnosis of OLTC at the first stage to provide early indication of OLTC's breakdown. The Static Winding Resistance Test is then applied at the second stage to figure out any increase of contact resistances for all phases. The capability of Static Winding Resistance Test in order to provide any sign of bad contacts in fixed condition can be done by comparing two different conditions which are before and after maintenance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.