Abstract

AbstractThe leakage current characteristic monitoring of transmission line insulators is considered a worthy technique for insulator state prediction. In this paper, the harmonic analysis of leakage current signals has been performed to analyze the composite insulator condition. Experimental studies of asymmetrically aged, fully aged, and virgin insulators have been conducted. The effects of different aging types, pollution, and humidity on leakage current components, such as harmonics and the phase differences with the applied voltage, have been investigated. The analysis of the results shows that the effect of asymmetric aging on leakage current components is non‐linear, and this non‐linearity increases with the degree of pollution. Also, the type of insulator aging can be determined by the ratio of the third‐ and fifth‐order leakage current harmonics. For instance, the classification of insulators into virgin, asymmetrically aged, and fully aged can be determined by examining the corresponding value ranges of 0–0.5, 0.5–0.9, and > 0.9, respectively. Similarly, the phase difference values of < 15% and those > 15% indicate the clean and polluted operating conditions individually.