Abstract

There has been a surge in the building of multimillion dollar homes along the California Coast. Often, large commercial style air conditioners are installed with multiple axial flow propeller condenser fans. They can generate low-frequency tones that annoy highly sensitive neighbors. By replacing 3- to 4-bladed stamped metal fans with a 6-, 9-, and 12-bladed highly efficient airfoil fan with pitch compensation, by reducing motor speeds from 1140 to 870 rpm, and by installing a variable speed controller, sound levels were reduced 14 dB @ 77 Hz as well as reducing energy consumption. This noise reduction solutions have proven to be far more effective than traditional barriers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.