Abstract

A method for predicting the local heat transfer coefficient is presented for film condensation of vapor in a spirally grooved horizontal microfin-tube. Based on the flow observation study performed by the present authors, film flow model between fins in the annular flow regime is proposed. For the fin surface, laminar condensate film controlled by the combined effects of vapor shear and surface tension forces is analyzed. While, in the groove, thick condensate film driven by the vapor shear force is taken into consideration. A parameter which accounts for the transition from annular-to stratified flow regimes is also derived. The present and previous local heat transfer data for fluorocarbon refrigerants in the annular flow regime are found by the present numerical analysis to have a mean absolute deviation of 15.1 percent.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.