Abstract

In this study, condensation heat transfer coefficients and frictional pressure drops of R-134a inside a dimpled helically coiled tube are experimentally investigated. The inner tubes comprise of one smooth straight tube, one smooth helically coiled tube and one dimpled helically coiled tube. The experimental measurements are carried out at saturation temperature of 35°, and 45 °C with mass flux of 75, 115, 156 and 191 kg m−2 s−1. The experimental data of a smooth and dimpled helically coiled tube have been plotted on the mass flux versus vapor quality flow map and Tailtel and Dukler flow map. The transitions between different flow regimes have also been discussed. Moreover, the effect of mass flux, vapor quality and saturation temperature of R-134a on the heat transfer coefficients and pressure drops are examined. Comparisons between smooth straight tube, smooth helically coiled tube and dimpled helically coiled tube are also discussed. The dimple helically coiled tube produces a higher heat transfer coefficient and frictional pressure drop compared to smooth helically coiled tube and smooth straight tube. The correlations have been proposed to predict the Nusselt number and frictional pressure drop multiplier during condensation of R-134a inside horizontal dimpled helically coil tube.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.