Abstract

In order to improve boiler efficiency, latent heat recovery from flue gas is a very important concept. Condensation heat transfer on horizontal stainless-steel tubes was investigated experimentally by using an actual flue gas from a natural gas boiler. The experiment was conducted at different air ratios of the flue gas and a wide range of tube wall temperatures. The condensation pattern was similar to a dropwise condensation near the dew point. By decreasing the wall temperature, the wall region covered with a thin liquid film increased. The heat and mass transfer behavior was well predicted with the analogy correlation at the high-wall-temperature region. At the low-wall-temperature region, the total heat transfer was higher than that predicted by the analogy correlation. © 2001 Scripta Technica, Heat Trans Asian Res, 30(2): 139–151, 2001

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.