Abstract

Heat transfer coefficients were measured for the condensation of R410A and R22 inside internally grooved horizontal tubes. The experiment was performed for five different kinds of internally grooved tubes of about 8.00 mm o.d. the shapes of which were conventional helical grooved and herring-bone grooved ones. To measure the local heat transfer coefficients, the test section was subdivided into 10 small sections having 1 m working length. The ranges tested are as follows: the refrigerant mass velocity was from 130 to 400 kg/(m2/s) for R410A and R22, and the vapour pressure was 2.4l MPa for R410A and 1.53 MPa for R22. The obtained heat transfer data of R410A and R22 indicate that the values of the local heat transfer coefficients of the herring-bone grooved tube are about twice as large as those of helical one. All measured local heat transfer coefficients of condensation were compared with the predicted values from previous correlations proposed by other researchers, and were well correlated with the empirical equation using the frictional coefficients for each tube proposed by the author.